Impacts thermique et hydraulique des générateurs de tourbillons à aile en delta sur la performance d'un échangeur de chaleur à tubes à ailettes simples.

The thermal-hydraulic impact of delta-wing vortex generators on the performance of a plain-fin-and-tube heat exchanger.

Auteurs : ELSHERBINI A. I., JACOBI A. M.

Type d'article : Article

Résumé

This article reports on experiments used to evaluate the effectiveness of delta-wing vortex generators applied to fin-and-tube heat exchangers. For air flowing at Reynolds numbers from about 700 to 2300, Colburn j and friction factor f data are obtained for a conventional refrigerator evaporator with and without a single row of delta-wing vortex generators placed at the inlet face of the test heat exchanger. Colburn j factor enhancements up to 31% over the baseline were obtained without any pressure-drop penalties.

Détails

  • Titre original : The thermal-hydraulic impact of delta-wing vortex generators on the performance of a plain-fin-and-tube heat exchanger.
  • Identifiant de la fiche : 2003-1733
  • Langues : Anglais
  • Source : HVAC&R Research - vol. 8 - n. 4
  • Date d'édition : 10/2002
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres articles du même numéro (6)
Voir la source