The thermal-hydraulic impact of delta-wing vortex generators on the performance of a plain-fin-and-tube heat exchanger.

Author(s) : ELSHERBINI A. I., JACOBI A. M.

Type of article: Article

Summary

This article reports on experiments used to evaluate the effectiveness of delta-wing vortex generators applied to fin-and-tube heat exchangers. For air flowing at Reynolds numbers from about 700 to 2300, Colburn j and friction factor f data are obtained for a conventional refrigerator evaporator with and without a single row of delta-wing vortex generators placed at the inlet face of the test heat exchanger. Colburn j factor enhancements up to 31% over the baseline were obtained without any pressure-drop penalties.

Details

  • Original title: The thermal-hydraulic impact of delta-wing vortex generators on the performance of a plain-fin-and-tube heat exchanger.
  • Record ID : 2003-1733
  • Languages: English
  • Source: HVAC&R Research - vol. 8 - n. 4
  • Publication date: 2002/10
  • Document available for consultation in the library of the IIR headquarters only.

Links


See other articles in this issue (6)
See the source