Installation d'un système d'irradiation à ultraviolets de type C (UVC) et son influence sur la qualité de l'air intérieur (IAQ).

Installation of a ultraviolet irradiation system, type C (UVC), plant and its influence on indoor air quality (IAQ).

Résumé

The authors investigated the effect of UVC on IAQ in a ventilation plant in a typical office building. The UVC-system consisted of UVC-lights for irradiation on all central components in the air handling unit. A similar ventilation plant, but without UVC, was chosen, as a reference plant. Microorganisms on surfaces, living airborne mould spores and MVOC (Microbial Volatile Organic Compounds) were sampled throughout the ventilation plant and in corresponding rooms before and after UVC-irradiation. In addition, parallel measurements in the reference plant were conducted. The number of colony forming units on surfaces were reduced in the "UVC-plant" after irradiation. For living airborne mould spores and MVOCs, no significant difference was observed. Conclusive UVC-systems seem in general to have little effect on IAQ in buildings with normal comfort ventilation plants.

Détails

  • Titre original : Installation of a ultraviolet irradiation system, type C (UVC), plant and its influence on indoor air quality (IAQ).
  • Identifiant de la fiche : 2004-2440
  • Langues : Anglais
  • Date d'édition : 15/06/2003
  • Source : Source : Pap. int. Conf. cold Clim. HVAC, Trondheim
    10 p.; fig.; tabl.; 14 ref.
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.