Installation d'un système d'irradiation à ultraviolets de type C (UVC) et son influence sur la qualité de l'air intérieur (IAQ).
Installation of a ultraviolet irradiation system, type C (UVC), plant and its influence on indoor air quality (IAQ).
Auteurs : PETTERSEN H., HANNEVOLD B., ØIE L.
Résumé
The authors investigated the effect of UVC on IAQ in a ventilation plant in a typical office building. The UVC-system consisted of UVC-lights for irradiation on all central components in the air handling unit. A similar ventilation plant, but without UVC, was chosen, as a reference plant. Microorganisms on surfaces, living airborne mould spores and MVOC (Microbial Volatile Organic Compounds) were sampled throughout the ventilation plant and in corresponding rooms before and after UVC-irradiation. In addition, parallel measurements in the reference plant were conducted. The number of colony forming units on surfaces were reduced in the "UVC-plant" after irradiation. For living airborne mould spores and MVOCs, no significant difference was observed. Conclusive UVC-systems seem in general to have little effect on IAQ in buildings with normal comfort ventilation plants.
Détails
- Titre original : Installation of a ultraviolet irradiation system, type C (UVC), plant and its influence on indoor air quality (IAQ).
- Identifiant de la fiche : 2004-2440
- Langues : Anglais
- Date d'édition : 15/06/2003
- Source : Source : Pap. int. Conf. cold Clim. HVAC, Trondheim
10 p.; fig.; tabl.; 14 ref. - Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.
Indexation
-
Ultraviolet germicidal irradiation: current bes...
- Auteurs : MARTIN S. B., DUNN C., FREIHAUT J. D., et al.
- Date : 08/2008
- Langues : Anglais
- Source : ASHRAE Journal - vol. 50 - n. 8
Voir la fiche
-
Using UVC (short-wave ultraviolet) technology t...
- Auteurs : SCHEIR R., FENCL F. B.
- Date : 02/1996
- Langues : Anglais
- Source : Heat. Pip. Air Cond. - 109-124; 3 fig.; 5 tabl.; 5 ref.
Voir la fiche
-
Tropical plants clean up the air.
- Auteurs : FOSTER D.
- Date : 21/06/1995
- Langues : Anglais
Voir la fiche
-
Applications de la stérilisation par irradiatio...
- Auteurs : LIU M., SHEN J., LIU C.
- Date : 01/2010
- Langues : Chinois
- Source : HV & AC - vol. 40 - n. 233
- Formats : PDF
Voir la fiche
-
Recommandations pour la prévention de la tuberc...
- Auteurs : HURE P., ABITEBOUL D., LEPRINCE A.
- Date : 10/1995
- Langues : Français
- Source : Chaud Froid Plomb./Chauff. Vent. Cond. - 79-82; 1 fig.; 9 ref.
Voir la fiche