Le R450[A] et le R513[A] comme substituts à faible GWP au R-134[A] et au R-507[A] dans un système frigorifique à température moyenne.

R450a and R513a as low-GWP substitutes of R-134a and R-507a in a medium temperature refrigeration system.

Numéro : pap. 1102

Auteurs : LLOPIS R., NEBOT-ANDRÉS L., CATALÁN-GIL J., et al.

Résumé

This work presents the experimental evaluation of R-513A (GWP=573) and R-450A (GWP=547) as drop-in replacements of R-134a (GWP=1301) and R-507A (GWP=3987) in a commercial cabinet using a direct expansion system for medium temperature applications. The evaluation covers 24-hour energy tests using a single-stage refrigeration cycle with semihermetic compressor, electronic expansion valve and a commercial vertical cabinet with doors placed inside a climatic chamber. Tests were done at three water dissipation temperatures (23.3, 32.8 and 43.6ºC) using a constant volumetric flow rate of 1 m3·h-1. The work focuses on temperature and pressure indicators in the refrigeration system, as well as, in the energy performance using the drop-in mixture against the high-GWP refrigerants.

Documents disponibles

Format PDF

Pages : 8

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : R450a and R513a as low-GWP substitutes of R-134a and R-507a in a medium temperature refrigeration system.
  • Identifiant de la fiche : 30024082
  • Langues : Anglais
  • Source : CYTEF 2018. IX Congreso Ibérico y VII Congreso Iberoamericano de Ciencias y Técnicas del Frío, Valencia, España, 19-21 junio 2018.
  • Date d'édition : 19/06/2018

Liens


Voir d'autres communications du même compte rendu (81)
Voir le compte rendu de la conférence