Document IIF

Les spécifications de conception des systèmes frigorifiques au Royaume-Uni sont-elles adaptées au climat actuel et futur ??

Are UK refrigeration design specifications fit for current and future climate?

Résumé

The performance of the refrigeration plant is directly affected by the surrounding temperature and humidity. The heatwave in 2022 saw temperatures in some parts of the UK exceed 40°C for the first time. Climate models predict peak temperatures exceeding 40°C regularly in the near future. The integrity of the cold chain rests upon proper functioning of refrigeration equipment. Although forward thinking designers are considering higher ambient temperatures, there is no standard or operating guidelines to steer industry in the right direction. This study carried out surveys and audits to investigate the preparedness of the cold chain to warmer ambient temperatures. Cold stores tend to have older plant (mean of 10.9 years) compared to retail (4.6 years). Condensing temperatures were often higher than optimum, with an example of 40°C recorded when the ambient was only 15°C.
This study recommends a standard method for choosing design ambient temperature, considering location in the UK and life of equipment.

Documents disponibles

Format PDF

Pages : 9 p.

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Are UK refrigeration design specifications fit for current and future climate?
  • Identifiant de la fiche : 30034167
  • Langues : Anglais
  • Sujet : Environnement
  • Source : 1st IIR International Conference on Refrigeration Adapting to Rising Temperatures
  • Date d'édition : 08/2025
  • DOI : http://dx.doi.org/10.18462/iir.adaptation.2024.1107

Liens


Voir d'autres communications du même compte rendu (45)
Voir le compte rendu de la conférence