Limites de charge des frigorigènes hydrocarbures pour les salles de repos.

Hydrocarbon refrigerant charge limits for quiescent rooms.

Auteurs : COLBOURNE D., SUEN K. O.

Type d'article : Article de la RIF

Résumé

Concentration measurements and analysis have been used to develop new methodology for estimating the allowable charge limit (ACL) of flammable refrigerants, particularly R290. Attention has been given to the impacts of construction and dimensional characteristics of the RACHP enclosures, in particular the size and position of the openings, on the concentrations exiting the enclosure. Analysis of the data has shown that these are critical aspects that influence floor concentration and/or safe allowable refrigerant charge limits. Formulae have been proposed to estimate layer-volume heights and ultimately ACL. The results illustrate that current standard's ACLs are overly restrictive, especially for certain types of RACHP equipment.

Documents disponibles

Format PDF

Pages : 75-83

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Hydrocarbon refrigerant charge limits for quiescent rooms.
  • Identifiant de la fiche : 30028262
  • Langues : Anglais
  • Sujet : Réglementation, Alternatives aux HFC
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 125
  • Date d'édition : 05/2021
  • DOI : http://dx.doi.org/10.1016/j.ijrefrig.2021.01.006