Document IIF

Minimisation de la charge dans des systèmes hydrocarbures.

Charge minimization in hydrocarbon systems.

Auteurs : HOEHNE M., HRNJAK P.

Résumé

The paper presents the results of the project to minimize the charge in a R290 system that has 1-1.5 kW refrigeration capacity. The major reduction of the charge was achieved by using microchannel heat exchangers. The system presented is charged with around 120 g. Analysis and new prototypes indicate that in the next step it will be possible to go below 50 g/kW at 1 kW basis. Besides experimental results, the paper presents analysis of the charge location, both in off and on condition. The results of the system model are compared to the experiments and indicate good prediction of capacity and charge.

Documents disponibles

Format PDF

Pages : 2004-2

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Charge minimization in hydrocarbon systems.
  • Identifiant de la fiche : 2005-2442
  • Langues : Anglais
  • Source : Natural Working Fluids 2004: 6th IIR-Gustav Lorentzen Conference
  • Date d'édition : 01/08/2004

Liens


Voir d'autres communications du même compte rendu (105)
Voir le compte rendu de la conférence