Document IIF
Modélisation dynamique et analyse caractéristique d’un système biétagé de pompe à chaleur à injection de vapeur sous des conditions de givrage.
Dynamic modeling and characteristic analysis of a two-stage vapor injection heat pump system under frosting conditions.
Auteurs : QIAO H., AUTE V., RADERMACHER R.
Type d'article : Article, Article de la RIF
Résumé
This paper presents a distributed-parameter dynamic heat exchanger model integrated with a detailed frost growth model to account for non-uniform frost formation on a fan-supplied finned-tube coil. A novel, iteration-free approach is proposed to solve the air flow redistribution by linearizing a system of non-linear air pressure drop equalization equations, resulting in a significant improvement in the computational efficiency. As a continuation and extension of our previous work, the developed models along with the component models described in Qiao et al. (2015a) are applied for the first time to explore the frosting dynamics of a two-stage flash tank vapor injection heat pump system. It is found that frost formation degrades the heating performance of the system substantially. Meanwhile, the simulation indicates that air and refrigerant flow maldistribution, resulting from non-uniform frost growth on the outdoor heat exchanger, can lead to unstable system hunting behavior. Comparisons between the simulation results and experimental data indicate that the proposed models can reasonably predict the time-dependent heat transfer and fluid flow phenomena of the system.
Documents disponibles
Format PDF
Pages : 181-197
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Dynamic modeling and characteristic analysis of a two-stage vapor injection heat pump system under frosting conditions.
- Identifiant de la fiche : 30022532
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 84
- Date d'édition : 12/2017
- DOI : http://dx.doi.org/10.1016/j.ijrefrig.2017.08.020
Liens
Voir d'autres articles du même numéro (26)
Voir la source
Indexation
-
Performance comparison of the vapor-injection c...
- Auteurs : ROH C. W., KIM M. S.
- Date : 16/07/2012
- Langues : Anglais
- Source : 2012 Purdue Conferences. 14th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
Voir la fiche
-
Performance comparison of air-source heat pumps...
- Auteurs : JIN L., YIN X., PAN S., et al.
- Date : 11/07/2016
- Langues : Anglais
- Source : 2016 Purdue Conferences. 16th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
Voir la fiche
-
Experimental results on a vapour injection scro...
- Auteurs : ZABET I., TÂRLEA G. M.
- Date : 2012
- Langues : Anglais
- Source : Buletinul Institutului politehnic din Iasi, Sectia Constructii de Masini - vol. 58 - n. 4
Voir la fiche
-
Comparison of borehole heat exchangers response...
- Auteurs : FOSSA M., MINCHIO F.
- Date : 05/04/2011
- Langues : Anglais
- Source : Sources/sinks Alternative to the Outside Air for Heat Pump and Air-conditioning Techniques (Alternative Sources - AS), Padua, Italy, April 5-7, 2011. / International Sorption Heat Pump Conference (ISHPC11), Padua, Italy, April 6-8, 2011.
- Formats : PDF
Voir la fiche
-
A Dynamic Model for Microchannel Heat Exchanger...
- Auteurs : LING J., WANG L., DHUMANE R., AUTE V.
- Date : 31/08/2021
- Langues : Anglais
- Source : 13th IEA Heat Pump Conference 2021: Heat Pumps – Mission for the Green World. Conference proceedings [full papers]
- Formats : PDF
Voir la fiche