Document IIF

Nouvelles données sur le transfert de masse dans un système à déshydratant liquide à écoulement croisé.

New mass transfer performance data of a crossflow liquid desiccant dehumidification system.

Auteurs : MOON C. G., BANSAL P. K., JAIN S.

Type d'article : Article, Article de la RIF

Résumé

This paper presents new mass transfer performance data of a crossflow liquid desiccant dehumidification system using a structured packed tower. The structured packing consists of cross-corrugated cellulose paper sheets with a surface area per unit volume ratio of 608 m2/m3. The liquid desiccant, viz. calcium chloride, flows through the pad from top to bottom, while the air flows horizontally making it a cross-flow configuration. The experimental dehumidification effectiveness from this study was compared with the widely used Chung's correlation (although developed for counter flow arrangement, as opposed to cross-flow in the current study) and Liu et al.'s correlation. A new empirical correlation was developed for the dehumidification effectiveness, which fitted the experimental data to within plus or minus 10%. The effect of varying air and solution inlet conditions and flow rates on the system performance was also quantified in the paper.

Documents disponibles

Format PDF

Pages : 524-533

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : New mass transfer performance data of a crossflow liquid desiccant dehumidification system.
  • Identifiant de la fiche : 2009-0745
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 32 - n. 3
  • Date d'édition : 05/2009

Liens


Voir d'autres articles du même numéro (18)