OPTIMISATION DE LA CONSOMMATION D'ENERGIE DES INSTALLATIONS DE REFROIDISSEURS UTILISANT UN SYSTEME DE COMMANDE ET REGULATION CENTRAL ET UNE REGULATION NUMERIQUE DIRECTE.

OPTIMIZATION OF CHILLER PLANT'S ENERGY CONSUMPTION UTILIZING A CENTRAL ENERGY MANAGEMENT AND CONTROL SYSTEM AND DIRECT DIGITAL CONTROL.

Auteurs : WILLIAMS V. A.

Résumé

QUELQUES POSSIBILITES INTERESSANTES D'ECONOMIE D'ENERGIE SONT DISPONIBLES, EN PARTICULIER SI LE SYSTEME DE COMMANDE ET DE REGULATION DE L'ENERGIE INFORMATISE DU BATIMENT COMPREND UNE REGULATION NUMERIQUE DIRECTE. CE SYSTEME PEUT LIRE LA POSITION EXACTE DE CHAQUE ROBINET DE COMMANDE DES ECHANGEURS FRIGORIFIQUES ET FIXER DE NOUVEAU LE POINT DE REGULATION DE LA TEMPERATURE D'ALIMENTATION EN EAU GLACEE. IL PEUT AUSSI MONITORER LA PRESSION DIFFERENTIELLE A L'EXTREMITE DE LA BOUCLE D'EAU GLACEE ET AJUSTER LE FLUX DE LA POMPE A EAU GLACEE. CE POINT DE REGULATION PEUT AUSSI ETRE FIXE DE NOUVEAU SUIVANT LA DEMANDE DU ROBINET DE L'ECHANGEUR FRIGORIFIQUE.

Détails

  • Titre original : OPTIMIZATION OF CHILLER PLANT'S ENERGY CONSUMPTION UTILIZING A CENTRAL ENERGY MANAGEMENT AND CONTROL SYSTEM AND DIRECT DIGITAL CONTROL.
  • Identifiant de la fiche : 1987-0347
  • Langues : Anglais
  • Date d'édition : 1985
  • Source : Source : ASHRAE Trans.
    vol. 91; n. 2B; 857-862; 1 fig.; discuss.