Patinoires utilisant le dioxyde de carbone comme frigoporteur.
Ice rinks using carbon dioxide as secondary refrigerant.
Auteurs : ROGSTAM J.
Résumé
The average Swedish ice rink annually uses about 1000 MWh, which is a total of electricity and heat. The refrigeration system accounts for 35-75% of the total energy usage depending on size and type of activity. When looking at indirect refrigeration systems, field measurements show that, provided capacity controlled motors are used, the distribution energy is about 20% of the total energy. Further, about half of that is related to the secondary refrigerant and brine pumps, thus being an interesting field for energy saving. The distribution energy reduces significantly by using CO2 as secondary refrigerant. The pump energy reduction is about 90% compared to a fixed speed CaCl2-solution and 50% compared to capacity controlled brine pumps. Recent developments related to pumps and secondary refrigerants have brought the traditional systems solutions with single-phase secondary refrigerant closer to CO2, hence further development is required. Experimental data on pump energy for traditional ice rink systems show that they require about 10% of the total refrigeration system energy, whereas the figure for an existing CO2-system is 3%, corresponding to a monthly saving of about 2000 kWh. Next generation CO2 system should profit from the possibility to utilise gravity circulation. A model proved that a reasonable liquid head, 2.5 m, is enough to cover an ice sheet heat load of up to 200 kW. This is well above the average heat load of about 150 kW for a normal ice rink. The economical aspect based on a LCC model and the results indicates that the proposed CO2-system is profitable provided the delta investment cost is limited to 75 kEuro, energy prices do not decrease from today's levels and the type of arena has an operation time of at least 8 months.
Documents disponibles
Format PDF
Disponible
Prix public
20 €
Prix membre*
15 €
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Ice rinks using carbon dioxide as secondary refrigerant.
- Identifiant de la fiche : 2011-0351
- Langues : Anglais
- Source : IIR/Eurotherm sustainable refrigeration and heat pump technology conference. Proceedings of the Eurotherm Seminar No. 88, Stockholm, Sweden, June 13-16, 2010.
- Date d'édition : 13/06/2010
Liens
Voir d'autres communications du même compte rendu (49)
Voir le compte rendu de la conférence
Indexation
-
Ice rink refrigeration system with CO2 as secon...
- Auteurs : ROGSTAM J., SAWALHA S., NILSSON P. O.
- Date : 02/08/2005
- Langues : Anglais
- Source : Commercial Refrigeration. Thermophysical Properties and Transfer Processes of Refrigerants. Proceedings of the IIR International Conferences.
- Formats : PDF
Voir la fiche
-
Ice rink refrigeration system with carbon dioxi...
- Auteurs : NILSSON P. O., ROGSTAM J., SAWALHA S., et al.
- Date : 29/05/2006
- Langues : Anglais
- Source : 7th IIR-Gustav Lorentzen Conference on Natural Working Fluids (GL2006). Proceedings
- Formats : PDF
Voir la fiche
-
Modelo de predicción de consumo de energía comp...
- Auteurs : KHALID W., ROGSTAM J.
- Date : 11/2013
- Langues : Espagnol
- Source : Frío Calor Aire acondicionado - vol. 41 - n. 463
- Formats : PDF
Voir la fiche
-
Energy usage prediction model comparing outdoor...
- Auteurs : KHALID W., ROGSTAM J.
- Date : 10/09/2012
- Langues : Anglais
- Source : 4th Jordanian IIR International Conference on Refrigeration and Air Conditioning. Proceedings: Amman, Jordan, September 10-12, 2012.
- Formats : PDF
Voir la fiche
-
Natural working fluids in artificial skating ri...
- Auteurs : BERENDS E.
- Date : 29/05/2006
- Langues : Anglais
- Source : 7th IIR-Gustav Lorentzen Conference on Natural Working Fluids (GL2006). Proceedings
- Formats : PDF
Voir la fiche