PERFORMANCE DU TRANSFERT DE CHALEUR ET DE MASSE DES REFROIDISSEURS D'AIR EN REGIME HUMIDE.

HEAT AND MASS TRANSFER PERFORMANCE OF AIR COOLERS UNDER WET CONDITIONS.

Résumé

LORSQU'IL S'AGIT DE L'EVALUATION DE LA PERFORMANCE DES REFROIDISSEURS D'AIR EN REGIME HUMIDE ON PEUT INDIQUER UN COEFFICIENT DE TRANSFERT D'ENTHALPIE EQUIVALENT ET UN COEFFICIENT DE TRANSFERT DE MASSE EQUIVALENT. CET ARTICLE MONTRE QUE LE COEFFICIENT DE TRANSFERT D'ENTHALPIE EQUIVALENT NE DEPEND PAS SEULEMENT DE LA TEMPERATURE ET DE L'HUMIDITE DE L'AIR, MAIS AUSSI DE LA TEMPERATURE SUPERFICIELLE DU TUBE, A CONDITION QUE LA CHALEUR ET LA MASSE SOIENT TRANSFEREES EN MEME TEMPS. DANS LE CAS D'UNE TEMPERATURE DE L'AIR CONSTANTE ET D'UNE HUMIDITE CONSTANTE, LE COEFFICIENT DE TRANSFERT D'ENTHALPIE EQUIVALENT EST FAIBLE, TANDIS QUE LA TEMPERATURE SUPERFICIELLE DU TUBE DU REFROIDISSEUR D'AIR EST ELEVEE. ON PEUT PREVOIR LE COEFFICIENT DE TRANSFERT D'ENTHALPIE EQUIVALENT EN N'UTILISANT QUE LE COEFFICIENT DE TRANSFERT DE CHALEUR SUPERFICIEL DE L'AILETTE DANS PLUSIEURS CONDITIONS DE TEMPERATURE ET D'HUMIDITE DE L'AIR.

Détails

  • Titre original : HEAT AND MASS TRANSFER PERFORMANCE OF AIR COOLERS UNDER WET CONDITIONS.
  • Identifiant de la fiche : 1984-0920
  • Langues : Anglais
  • Date d'édition : 1981
  • Source : Source : ASHRAE Trans.
    vol. 87; n. 2; 109-115; 9 fig.; 2 ref.
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.