Potentiel d'économies d'énergie grâce aux diagnostics de la performance : rapport sur l'évaluation issue de 170 inspections sur le terrain avec la "méthode interne".

Potential of energy saving by performance inspections, report from the evaluation of 170 detailed field inspections with the "internal method".

Auteurs : BERGLÖF K., PRAKASH J.

Résumé

The paper introduces two methods, the "internal" and "external" for performance inspections on refrigeration, air-conditioning and heat pump systems. It reports results from 164 performance analyses done with the "internal" method. The data has been entered into a database and the deviations from nominal data have been evaluated as well as the type of faults. In total 87% of the systems had one or more faults documented. The average deviation from nominal capacity is -8.6% and the deviation in COP is -9.7%. The most common problems are wrong charge and problems with expansion valves. The internal method is increasingly in use for maintenance, inspections and integrated in building management systems for continuous monitoring. It has proved to identify a large number of faults. It offers a possibility for significantly improved "performance inspections" to satisfy the intentions of article 9 in the Energy performance in buildings Directive.

Documents disponibles

Format PDF

Pages : 2006-5

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Potential of energy saving by performance inspections, report from the evaluation of 170 detailed field inspections with the "internal method".
  • Identifiant de la fiche : 2007-1244
  • Langues : Anglais
  • Source : Compressors 2006: 6th International Conference on Compressors and Coolants
  • Date d'édition : 27/09/2006

Liens


Voir d'autres communications du même compte rendu (48)
Voir le compte rendu de la conférence