Document IIF

Pression optimale de la chaleur rejetée dans des conditionneurs d'air et des pompes à chaleur transcritiques utilisant du dioxyde de carbone.

Optimal heat rejection pressure in transcritical carbon dioxide air conditioning and heat pump systems.

Auteurs : LIAO S., JAKOBSEN A.

Résumé

In systems such as automobile air-conditioners and heat pumps, owing to the relatively high heat rejection temperatures, the cycles using carbon dioxide as refrigerant will have to operate in the transcritical area. Then, there is an optimal heat rejection pressure that gives a maximum COP. The value of this optimal heat rejection pressure mainly depends on the outlet temperature of the gas cooler, the evaporation temperature and the efficiency of the compressor. Correlations are given, providing basis for designing transcritical carbon dioxyde systems.

Documents disponibles

Format PDF

Pages : p 346-356

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Optimal heat rejection pressure in transcritical carbon dioxide air conditioning and heat pump systems.
  • Identifiant de la fiche : 1999-2826
  • Langues : Anglais
  • Source : Natural Refrigerants, Energy Efficiency, Cost and Safety. Natural Working Fluids '98. IIR-Gustav Lorentzen Conference.
  • Date d'édition : 02/06/1998

Liens


Voir d'autres communications du même compte rendu (65)
Voir le compte rendu de la conférence