Document IIF

Etude expérimentale de la performance d'un système à CO2/DME (diméthyléther).

Experimental study on the performance of a CO2/DME system.

Auteurs : KOYAMA S., JIN D. X., XUE J., et al.

Résumé

In this study, the binary mixture CO2/DME (90/10 wt%) was proposed as an alternative refrigerant for CO2 to reduce the high-operating pressure associated with CO2 transcritical refrigeration system. The performances of CO2/DME and pure CO2 systems were experimentally investigated using the same equipment in the conditions of constant heating/cooling capacity and superheat. Experimental results show, compared to the pure CO2 system, that the CO2/DME system operates with almost the same maximum COPs, and considerably lower discharge pressures in both the heating mode and the cooling mode. In the maximum COP condition, the CO2/DME system can reduce the discharge pressure by about 2 MPa in the heating mode and about 1.9 MPa in the cooling mode.

Documents disponibles

Format PDF

Pages : ICR07-E2-986

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Experimental study on the performance of a CO2/DME system.
  • Identifiant de la fiche : 2007-2475
  • Langues : Anglais
  • Source : ICR 2007. Refrigeration Creates the Future. Proceedings of the 22nd IIR International Congress of Refrigeration.
  • Date d'édition : 21/08/2007

Liens


Voir d'autres communications du même compte rendu (839)
Voir le compte rendu de la conférence