Document IIF

R410A : débit massique dans des tubes courts, proche du point critique.

Mass flow rate of R410A through short tubes working near the critical point.

Auteurs : KIM Y., PAYNE V., CHOI J., et al.

Type d'article : Article, Article de la RIF

Résumé

Experimental data were taken to examine R410A mass flow rate characteristics through short tube restrictors at upstream pressures approaching the critical point. Four short tube restrictors were tested by varying upstream pressure from 2619 to 4551 kPa (corresponding to saturation temperature from 43.9 to 71.7 °C), upstream subcooling from 2.8 to 11.1 °C and downstream pressure from 772 to 1274 kPa. The experimental data were represented as a function of major operating parameters and short tube diameter. As compared to mass flow trends at typical upstream pressures, flow dependency on upstream subcooling was more significant at high upstream pressures due to a higher density change. Based on the database obtained from this study and literature, an empirical correlation was developed from a power law form of dimensionless parameters generated by the Buckingham Pi theorem. The post-predictions of the new correlation yielded average and mean deviations of 0.11 and 2.4%, respectively.

Documents disponibles

Format PDF

Pages : 547-553

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Mass flow rate of R410A through short tubes working near the critical point.
  • Identifiant de la fiche : 2005-1633
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 28 - n. 4
  • Date d'édition : 06/2005

Liens


Voir d'autres articles du même numéro (16)
Voir la source