Recherche expérimentale sur le procédé de dégivrage d'un ventilateur de refroidissement avec dispositif de dégivrage à isolation thermique.

[In Chinese. / En chinois.]

Auteurs : SHEN J., LU K., LI H., et al.

Type d'article : Article

Résumé

In order to reduce the effect of defrosting heat on the cold storage temperature change during defrosting process, a heat insulation defrosting device is additionally provided to the air cooler in the storage,and the experimental study on the defrosting process was carried out. The results showed that in the defrosting processes with and without heat insulation, the temperature of the upper area in the storage changed greatly. The temperature changes relatively small during the defrosting process with heat insulation,and the overall fluctuating temperature is 3.2°C lower than that without heat insulation. In the meantime, the defrosting time with heat insulation is shortened by nearly 300s, which proves that the insulation defrosting device can stabilize the storage temperature and shorten the defrosting time in the defrosting process.

Documents disponibles

Format PDF

Pages : 104-107

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails


Liens


Voir d'autres articles du même numéro (8)
Voir la source