Transfert de chaleur lors de la condensation en écoulement du CO2 dans des microcanaux.

[ In Korean. / En coréen.]

Résumé

CO2 flow condensation heat transfer coefficients are investigated for 0.89 mm microchannels at horizontal flow conditions. They were measured at saturation temperatures of -15 and -25°C, mass fluxes from 200 to 800 kg/m2.s, and wall subcooling temperatures from 2 to 4°C. Measured heat transfer coefficients increased with the increase of mass fluxes and vapour qualities, whereas they were almost independent of wall subcooling temperature changes. Several correlations, developed from experimental data for the macro-scale tubes, could predict heat transfer coefficients within acceptable error range.

Détails

  • Titre original : [ In Korean. / En coréen.]
  • Identifiant de la fiche : 2009-1058
  • Langues : Coréen
  • Source : 3e Congrès coréen du froid.
  • Date d'édition : 19/03/2009

Liens


Voir d'autres communications du même compte rendu (29)
Voir le compte rendu de la conférence