In order to verify the mathematical model of an ice bank system developed for the purpose of predicting the system performance, experimental measurements on the ice bank system were performed. Static, indirect, cool thermal storage system, with an external ice-on-coil building/melting was considered. Cooling energy stored in the form of ice by night is used for the rapid cooling of milk after the process of pasteurization by day. The ice bank system was tested under real operating conditions to determine parameters such as the time-varying heat load imposed by the consumer, refrigeration unit load, storage capacity, supply water temperature to the load and to find charging and discharging characteristics of the storage. Experimentally obtained results were then compared to the computed ones. It was found that the calculated and experimentally obtained results are in good agreement as long as there is ice present in the silo. See also the Bulletin of the IIR, reference 2009-2082.

Documents disponibles

Format PDF

Pages : pp. 1657-1669

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Development of a computer program for the simulation of ice-bank system operation. II. Verification.
  • Identifiant de la fiche : 2010-1941
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 33 - n. 8
  • Date d'édition : 12/2010

Liens


Voir d'autres articles du même numéro (20)
Voir la source