Effet de l'utilisation de basses températures pour un système de conditionnement d'air à accumulation thermique.

[In Japanese. / En japonais.]

Auteurs : KARINO N., SHIBA T., YOKOYAMA R., et al.

Type d'article : Article

Résumé

The purpose of this paper was to propose an optimal operational planning method for an air-conditioning system with an ice storage unit, and to analyse the effect through a numerical study for an office building. The results are summarized as follows: 1) with an ice storage system allowing use of cheap electric power during the night, energy charges are reduced by about 40%; 2) reduced ventilation energy due to lower air temperature overcomes the higher cost of low-temperature chilled water.

Détails

  • Titre original : [In Japanese. / En japonais.]
  • Identifiant de la fiche : 2003-2958
  • Langues : Japonais
  • Source : Transaction of the Society of Heating, Air-conditioning and Sanitary Engineers of Japan - n. 82
  • Date d'édition : 07/2001
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres articles du même numéro (3)
Voir la source