Document IIF

Étude expérimentale d'un système de pompe à chaleur au CO2 transcritique avec un éjecteur en conditions hors-conception.

Experimental investigation on transcritical CO2 heat pump system with ejector in off-design conditions.

Numéro : pap. n. 61

Auteurs : WEI J., CHEN Q., TANG L., et al.

Résumé

The use of ejectors is one of the most promising methods to improve performance of transcritical CO2 heat pump systems. However, in this experimental study, transcritical CO2 heat pump system with ejector (TCHSE) is found to be inferior to conventional transcritical CO2 heat pump system (TCHS) in coefficient of performance (COP) when hot water outlet temperature is higher than a certain value. Thus, the use of ejector in CO2 heat pump water heater might not be beneficial under some working conditions. In this paper, off-design performance characteristics of the systems are analysed. Experimental investigations and assessments on performance of TCHS and TCHSE in off-design conditions are also carried out.

Documents disponibles

Format PDF

Pages : 8 p.

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Experimental investigation on transcritical CO2 heat pump system with ejector in off-design conditions.
  • Identifiant de la fiche : 30015096
  • Langues : Anglais
  • Source : Proceedings of the 24th IIR International Congress of Refrigeration: Yokohama, Japan, August 16-22, 2015.
  • Date d'édition : 16/08/2015
  • DOI : http://dx.doi.org/10.18462/iir.icr.2015.0061

Liens


Voir d'autres communications du même compte rendu (657)
Voir le compte rendu de la conférence