Étude expérimentale des caractéristiques de démarrage d’un compresseur rotatif au R290 dans des conditions de chauffage à basse température ambiante.

Experimental investigation of startup characteristics of R290 rotary compressor under low ambient temperature heating condition.

Auteurs : LIN J., WU J., ZHANG Z., et al.

Type d'article : Article, Article de la RIF

Résumé

The cold and warm startup characteristics of an R290 heat pump system and its rotary compressor were experimentally investigated under a low ambient temperature heating condition. These startup characteristics included the temperatures in the compressor shell and system and the pressures in the cylinder and system.The results showed that the minimum suction gauge pressure (-48 kPa) during a cold startup was lower than that during a warm startup (155 kPa) under a low ambient temperature heating condition. In addition, the time required for the R290 heat pump system to reach a steady pressure was much longer than
that of a system using R410A as the refrigerant. Compared with that of the cooling condition, smaller amounts of liquid were generated in the cylinder at the beginnings of both the cold and warm startup processes under the low ambient temperature heating condition.

Documents disponibles

Format PDF

Pages : 128-135

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Experimental investigation of startup characteristics of R290 rotary compressor under low ambient temperature heating condition.
  • Identifiant de la fiche : 30022287
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 77
  • Date d'édition : 05/2017
  • DOI : http://dx.doi.org/10.1016/j.ijrefrig.2017.02.029

Liens


Voir d'autres articles du même numéro (12)
Voir la source