Document IIF

Évaluation expérimentale du HC-290 comme frigorigène de remplacement immédiat du HCFC-22 dans les conditionneurs d'air de type split.

Experimental assessment of HC-290 as a drop-in substitute to HCFC-22 in a split air conditioner.

Numéro : pap. n. 11

Auteurs : SARAVANAN A. L., LAL D. M.

Résumé

A widely used refrigerant in split air conditioning units, the HCFC-22 has to be phased out by 2030 in all Article 5 countries under the Montreal Protocol. Propane (HC-290) is an alternative for HCFC-22. A 5.25 kW Split air conditioner without liquid receiver designed for HCFC-22 was retrofitted with HC-290 and tested under DT, ETA, ETB condition. Under drop-in tests, 4 suction line lengths viz: 12.37m, 19.1m, 23.75m, 30.1m were considered. Considering safety norms & density of HC-290 the charge quantity for HC-290 was taken to be 50% of the original HCFC-22 charge. The results show that as the suction line length increases ,the refrigeration capacity of propane reduces by 18.6% for lower operating conditions and 10.0% for the higher operating condition. The power consumption with HC-290 was lower by 4.28%. The COP with HC-290 was 17.8% higher for the lower operating conditions and 10.96% higher for the higher operating condition.

Documents disponibles

Format PDF

Pages : 7 p.

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Experimental assessment of HC-290 as a drop-in substitute to HCFC-22 in a split air conditioner.
  • Identifiant de la fiche : 30006404
  • Langues : Anglais
  • Source : RCR 2012. 3rd IIR Workshop on Refrigerant Charge Reduction in Refrigerating Systems: Valencia, Spain, October 25-26, 2012.
  • Date d'édition : 25/10/2012

Liens


Voir d'autres communications du même compte rendu (21)
Voir le compte rendu de la conférence