Experimental assessment of HC-290 as a drop-in substitute to HCFC-22 in a split air conditioner.
Number: pap. n. 11
Author(s) : SARAVANAN A. L., LAL D. M.
Summary
A widely used refrigerant in split air conditioning units, the HCFC-22 has to be phased out by 2030 in all Article 5 countries under the Montreal Protocol. Propane (HC-290) is an alternative for HCFC-22. A 5.25 kW Split air conditioner without liquid receiver designed for HCFC-22 was retrofitted with HC-290 and tested under DT, ETA, ETB condition. Under drop-in tests, 4 suction line lengths viz: 12.37m, 19.1m, 23.75m, 30.1m were considered. Considering safety norms & density of HC-290 the charge quantity for HC-290 was taken to be 50% of the original HCFC-22 charge. The results show that as the suction line length increases ,the refrigeration capacity of propane reduces by 18.6% for lower operating conditions and 10.0% for the higher operating condition. The power consumption with HC-290 was lower by 4.28%. The COP with HC-290 was 17.8% higher for the lower operating conditions and 10.96% higher for the higher operating condition.
Available documents
Format PDF
Pages: 7 p.
Available
Public price
20 €
Member price*
Free
* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).
Details
- Original title: Experimental assessment of HC-290 as a drop-in substitute to HCFC-22 in a split air conditioner.
- Record ID : 30006404
- Languages: English
- Source: RCR 2012. 3rd IIR Workshop on Refrigerant Charge Reduction in Refrigerating Systems: Valencia, Spain, October 25-26, 2012.
- Publication date: 2012/10/25
Links
See other articles from the proceedings (21)
See the conference proceedings
Indexing
-
Flammable refrigerant leakage hazards control f...
- Author(s) : NING Q., HE G., FAN M., XIONG J., LI X.
- Date : 2022/12
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 144
- Formats : PDF
View record
-
Refrigerant leakage control for R-290 in split ...
- Author(s) : COLBOURNE D., HÜHREN R., RAJADHYAKSHA D. D., et al.
- Date : 2013/09/02
- Languages : English
- Source: Compressors 2013: 8th International Conference on Compressors and Coolants.
- Formats : PDF
View record
-
Indoor leakage test for safety of R-290 split t...
- Author(s) : LI T.
- Date : 2014/04
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 40
- Formats : PDF
View record
-
Use of peripheral fins for R-290 charge reducti...
- Author(s) : RIBEIRO G. B., BARBOSA J. Jr
- Date : 2019/10
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 106
- Formats : PDF
View record
-
R290 leakage hazards assessment of a 1 HP split...
- Author(s) : NING Q., HE G., SUN W., FAN M., LI X., HONG Z.
- Date : 2022/07
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 139
- Formats : PDF
View record