Document IIF

Introduction d'une notation énergétique "energy goodness" dans les systèmes frigorifiques de supermarchés.

Introduction of an "energy goodness" number for supermarket refrigeration systems.

Auteurs : RASMUSSEN B. D., MUNTER P., HOLM H. V., et al.

Résumé

The test method is based on a combination of measurements of air temperatures and energy consumption on an actual system and calculations of the energy consumption for a reference refrigeration system whose characteristics are defined in each case. The energy efficiency of the system is expressed by a "Goodness Number" defined as the ratio between the calculated energy consumption of the reference system and the measured energy consumption for the actual system. Four different Danish supermarkets have been tested. "Goodness numbers" range from 0.42 to 0.75.

Documents disponibles

Format PDF

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Introduction of an "energy goodness" number for supermarket refrigeration systems.
  • Identifiant de la fiche : 2000-1499
  • Langues : Anglais
  • Source : 20th International Congress of Refrigeration: Refrigeration into the Third Millennium.
  • Date d'édition : 19/09/1999

Liens


Voir d'autres communications du même compte rendu (447)