Résumé
In this study, ‘drop-in’ performance of HFC-134a, HFO-1234yf and HFO-1234yf/HFC-134a mixture at three compositions of 5, 10, and 15% HFC-134a is measured in a heat pump bench tester under summer and winter conditions. Test results show that the COP, capacity, discharge temperature of HFO-1234yf and HFO-1234yf/HFC-134a mixture are similar to those of HFC-134a. For HFO-1234yf/HFC-134a mixture, flammability decreases as more HFC-134a is added and at compositions of more than 10% of HFC-134a, the mixture becomes non-flammable. The amount of charge for HFO-1234yf and HFO-1234yf/HFC-134a mixture is up to 11% lower than that of HFC-134a. Since HFO-1234yf/HFC-134a mixture with 10-11% HFC-134a is non-flammable and azeotropic and has no ODP and GWP of less than 150 meeting the requirement of European mobile air-conditioner directive, it can be used as a long term environmentally friendly solution for various HFC-134a applications including mobile air conditioners with minor modifications.
Détails
- Titre original : Performance of non-flammable azeotropic HFO-1234yf/HFC-134a mixture for HFC-134a applications.
- Identifiant de la fiche : 30006105
- Langues : Anglais
- Sujet : Alternatives aux HFC
- Source : Inha University, Department of Mechanical Engineering, Incheon
- Date d'édition : 2012
Liens
Voir la source
Indexation
-
Performance of virtually non-flammable azeotrop...
- Auteurs : LEE Y., KANG D. G., JUNG D.
- Date : 06/2013
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 36 - n. 4
- Formats : PDF
Voir la fiche
-
Drop-in performance analysis and effect of IHX ...
- Auteurs : DIREK M., KELESOGLU A., AKIN A.
- Date : 05/2017
- Langues : Anglais
- Source : Strojniski vestnik - Journal of mechanical Engineering - vol. 63 - n. 5
- Formats : PDF
Voir la fiche
-
Second law analysis of an automotive air condit...
- Auteurs : GOLZARI S., KASAEIAN A., DAVIRAN S., et al.
- Date : 01/2017
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 73
- Formats : PDF
Voir la fiche
-
Flammability investigation of different refrige...
- Auteurs : GRAZ M., WUITZ U.
- Date : 02/2008
- Langues : Anglais
- Source : Obrist Eng. - 28 p.; fig.; phot.; tabl.; append.
Voir la fiche
-
Alternative refrigerant is flammable and toxic.
- Date : 12/2008
- Langues : Anglais
- Source : ScanRef - vol. 37 - n. 6
Voir la fiche