Document IIF

Performance d'une pompe à chaleur transcritique au CO2, conçue pour l'industrie alimentaire.

Performance of a transcritical CO2 heat pump for the food processing industries.

Résumé

New Zealand food processing industries have a simultaneous need for refrigeration below 10 deg C and heating of water to greater than 80 deg C. A prototype transcritical CO2 heat pump was constructed for this purpose. The combined heating and cooling COP of the prototype was about 5 when producing hot water at 90 deg C and refrigeration at less than 0 deg C. This performance could be further improved if a higher efficiency compressor was used and the heat exchanger sizes were optimised. The market potential for the technology is good (well matched to the requirements of many food processing industries, high energy efficiency).

Documents disponibles

Format PDF

Pages : 9 p.

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Performance of a transcritical CO2 heat pump for the food processing industries.
  • Identifiant de la fiche : 1999-2819
  • Langues : Anglais
  • Source : Natural Refrigerants, Energy Efficiency, Cost and Safety. Natural Working Fluids '98. IIR-Gustav Lorentzen Conference.
  • Date d'édition : 02/06/1998
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres communications du même compte rendu (65)
Voir le compte rendu de la conférence