Régulation de la température de l’eau froide à la sortie d’un réfrigérateur à adsorption alimenté par des rejets thermiques.

Controlling the cold-water temperature at the outlet of an adsorption refrigerator driven by exhaust heat.

Numéro : AD-YR2-1120

Auteurs : MATSUDA Y., KOGANEI M., KUWAHARA R., et al.

Résumé

This study investigates the mechanism for ensuring a constant cold-water temperature in an adsorption refrigerator by adjusting the amount of cooling water with a three-stage process over one cycle. It is determined that it is possible to secure a continuous cooling capacity by installing a bypass route from the inlet side of heat exchanger (HEX) to the condenser. We confirmed that the cooling capacity is 6.87 kW, which is 80% of the rated value, and the mean deviation of the cold-water temperature is ± 0.18 °C.

Détails

  • Titre original : Controlling the cold-water temperature at the outlet of an adsorption refrigerator driven by exhaust heat.
  • Identifiant de la fiche : 30023095
  • Langues : Anglais
  • Source : International sorption heat pump conference, ISHPC 2017, Tokyo august 7-10.
  • Date d'édition : 07/08/2017