Test de performance d’un refroidisseur à température moyenne équipé d’unités de traitement de l’air à induction appliqué à des immeubles de bureaux.

[In Chinese. / En chinois.]

Auteurs : WANG Z., WANG G., LIU S., et al.

Type d'article : Article

Résumé

Presents the working principle of medium temperature chiller with induction air unit system. It obtains supply air temperature of 13°C by extensive type air handling unit with fin oval tube heat exchanger. Tests the temperature, relative humidity and energy consumption in an office building with this system in summer of 2013. The results show that both of indoor temperature and humidity keep n the design range. The dew point temperature of indoor air is much lower than the supply air temperature from air inductive unit, without condensed water or condensation on the surface of air inductive unit. The performance of the circulation pump, fan in the extensive type air handling unit and medium temperature chiller is better than the requirements of national standards.

Documents disponibles

Format PDF

Pages : 58-61

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : [In Chinese. / En chinois.]
  • Identifiant de la fiche : 30018380
  • Langues : Chinois
  • Source : HV & AC - vol. 45 - n. 311
  • Date d'édition : 11/2015

Liens


Voir d'autres articles du même numéro (2)
Voir la source