Recommandé par l'IIF / Document IIF
Effets des défaillances courantes sur une pompe à chaleur à vitesse variable fonctionnant avec un frigorigène naturel.
Common fault effects on a natural refrigerant, variable-speed heat pump.
Auteurs : BELLANCO I., BELIO F., VALLES M., GERBER R., SALOM J.
Type d'article : Article de la RIF
Résumé
The European heat pump market is growing every year as European legislation moves towards the use of natural refrigerants that have less global warming potential than conventional refrigerants. Even though heat pumps are very efficient, the appearance of hard-to-detect faults increases energy consumption. The present study emulated some of the most common faults on a variable-speed heat pump charged with propane. The faults tested were evaporator fouling, compressor valve leakage, liquid line restriction and refrigerant overcharge. The effect of these faults on performance and several heat pump features are described. Evaporator fouling was the fault with least COP degradation and compressor valve leakage with the most (7% and 56% COP reduction, respectively). The results are compared with the results from a comparable study. The heat pump covered the demand generated by nearly all the faults at the expense of increasing the power consumption. The features of each fault are summarized in a chart, which could be used as table for diagnosing faults.
Documents disponibles
Format PDF
Pages : 259-266
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Common fault effects on a natural refrigerant, variable-speed heat pump.
- Identifiant de la fiche : 30029278
- Langues : Anglais
- Sujet : Technologie, Alternatives aux HFC
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 133
- Date d'édition : 01/2022
- DOI : http://dx.doi.org/10.1016/j.ijrefrig.2021.10.017
- Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.
Liens
Voir d'autres articles du même numéro (32)
Voir la source
Indexation
-
A propane hydronic heat pump with energy storage.
- Auteurs : SHEN B., LI Z., WAN H., GLUESENKAMP K., FRICKE B.
- Date : 21/08/2023
- Langues : Anglais
- Source : Proceedings of the 26th IIR International Congress of Refrigeration: Paris , France, August 21-25, 2023.
- Formats : PDF
Voir la fiche
-
Refrigerant charge distribution in brine-to-wat...
- Auteurs : SANCHEZ MORENO GINER L., METHLER T., BARCELÓ RUESCAS F., GONZÁLVEZ-MACIÁ J.
- Date : 01/2023
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 145
- Formats : PDF
Voir la fiche
-
Experimental results of a high efficient booste...
- Auteurs : PITARCH M., GONZÁLVEZ-MACIÁ J., NAVARRO-PERIS E., et al.
- Date : 21/08/2016
- Langues : Anglais
- Source : 12th IIR Gustav Lorentzen Conference on Natural Refrigerants (GL2016). Proceedings. Édimbourg, United Kingdom, August 21st-24th 2016.
- Formats : PDF
Voir la fiche
-
Coupling effects in fault detection and diagnos...
- Auteurs : LLOPIS-MENGUAL B., NAVARRO-PERIS E.
- Date : 21/08/2023
- Langues : Anglais
- Source : Proceedings of the 26th IIR International Congress of Refrigeration: Paris , France, August 21-25, 2023.
- Formats : PDF
Voir la fiche
-
Investigation of a heat pump dishwasher with Na...
- Auteurs : STOECKEL K., MICKOLEIT E., BUSHING F., BARTA R. B., THOMAS C.
- Date : 21/08/2023
- Langues : Anglais
- Source : Proceedings of the 26th IIR International Congress of Refrigeration: Paris , France, August 21-25, 2023.
- Formats : PDF
Voir la fiche