Document IIF

Méthode de détection de la charge en frigorigène d’un système de conditionnement d’air à débit de frigorigène variable (VRF) utilisant l’apprentissage par empilement d’ensembles. 

A variable refrigerant flow (VRF) air-conditioning system refrigerant charge detection method using stacking ensemble learning.

Numéro : 0936

Auteurs : CHENG H., MU W., CHENG Y., CHEN H., XING L.

Résumé

This paper proposes a stacking ensemble learning method to detect the refrigerant charge fault of the variable refrigerant flow (VRF) air conditioning system. Firstly, measurement data is collected from the refrigerant charge fault experiment of a VRF system performed in an enthalpy difference laboratory. Several features are selected based on different criteria after preprocessing the measurement data and importance analysis. To prevent overfitting, no duplicate dataset is created. Then, five classification models have been used in this paper as follows: Support Vector Machine (SVM), Gradient Boosting Machine (GBM), Random Forest (RF), Multi-layer Perceptron (MLP), and K-Nearest Neighbors (KNN). After several parameter optimizations, these models demonstrate accuracy between 84.71% to 91.58%. Finally, different stacking ensemble learning methods integrate these models, achieving the test set's best accuracy rate (96.66%).

Documents disponibles

Format PDF

Pages : 14

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : A variable refrigerant flow (VRF) air-conditioning system refrigerant charge detection method using stacking ensemble learning.
  • Identifiant de la fiche : 30031850
  • Langues : Anglais
  • Sujet : Technologie
  • Source : Proceedings of the 26th IIR International Congress of Refrigeration: Paris , France, August 21-25, 2023.
  • Date d'édition : 21/08/2023
  • DOI : http://dx.doi.org/10.18462/iir.icr.2023.0936

Liens


Voir d'autres communications du même compte rendu (492)
Voir le compte rendu de la conférence