IIR document

Analytical modeling of a desiccant wheel.

Author(s) : LEE D. Y., KIM D. S.

Type of article: Article, IJR article

Summary

A simple integral model is presented for a desiccant wheel. The original governing equations for a desiccant wheel were simplified to a set of linear ordinary differential equations and an analytical solution was obtained. A brief analysis is given about the solution regarding the non-dimensional numbers that decide the behavior of a desiccant wheel. From the solution, algebraic expressions were obtained for time-averaged heat and mass transfer rates and the results were compared with a numerical model and a set of experimental data in the literature. In comparison with the numerical model, relative error was found less than 12% at 120°C regeneration temperature and 10% standard deviation was observed with the experimental data. The analytical model is considered capable of describing a symmetric desiccant wheel realistically.

Available documents

Format PDF

Pages: 97-111

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Analytical modeling of a desiccant wheel.
  • Record ID : 30011404
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 42
  • Publication date: 2014/06

Links


See other articles in this issue (12)
See the source