Heat transfer characterization of plate fin-tube heat exchangers.

Author(s) : KAYANSAYAN N.

Type of article: Article

Summary

The effects upon the performance of plate fin-tube cross flow heat exchangers due to outer surface geometry are considered. The finning parameter varying through 11 to 23, a total of ten geometrically distinct configurations were tested over a Reynolds number range from 100 to 30,000. The tube outside diameter with the collar thickness defines the characteristic dimension. The convective heat transfer coefficients are presented as plots of Colburn j-factor versus Reynolds number and compare well with previous studies. Typical data spread being more or less 10 percent range, the j-factor, the Reynolds number, and the finning parameter are correlated.

Details

  • Original title: Heat transfer characterization of plate fin-tube heat exchangers.
  • Record ID : 1993-2567
  • Languages: English
  • Source: Heat Recov. Syst. CHP - vol. 13 - n. 1
  • Publication date: 1993/01

Links


See other articles in this issue (5)
See the source