Performance and internal flow of cross-flow fan with inlet guide vane.
Author(s) : FUKUTOMI J., NAKAMURA R.
Type of article: Article
Summary
The effect of angle and length of the inlet guide vane on the performance of the cross-flow fan is examined. By installing guide vane of one sheet in tongue division side in the suction region, the performance of the cross-flow fan becomes more high pressure and high efficient than the case without the guide vane. The prerotation of the inlet flow which is counter directional with the rotation of the rotor is generated by the guide vane. In the high flow region, the high pressure and high efficiency are obtained since the suction cascade work increases by the prerotation of the flow, and since the leading edge separation of the suction cascade is more avoided to high flow. Moreover, in the flow region, it is possible to suppress the circulating flow in scroll side in the rotor suction inlet. Therefore, the high efficiency is obtained in the low power compared to the result without the guide vane.
Details
- Original title: Performance and internal flow of cross-flow fan with inlet guide vane.
- Record ID : 2006-2582
- Languages: English
- Source: JSME int. J., B - vol. 48 - n. 4
- Publication date: 2005/11
Links
See other articles in this issue (1)
See the source
Indexing
- Themes: Other air-conditioning equipment
- Keywords: Enhancement; Centrifugal fan; Design; Performance
-
Ventilatore centrifugo. Effetto del gioco all'a...
- Author(s) : OSNAGHI C., GAETANI P.
- Date : 1998/06
- Languages : Italian
- Source: Termotecnica - vol. 52 - n. 5
View record
-
Unhoused (plug/plenum) fans: is their performan...
- Author(s) : COWARD C. W.
- Date : 1997/10
- Languages : English
- Source: ASHRAE Journal - vol. 39 - n. 10
View record
-
Procena uticaja instalisanja unutrasnjeg ventil...
- Author(s) : LAI C. M., CHEN K. R., LEE C. Y.
- Date : 2005/11/02
- Languages : Serbian
- Source: Zbornik radova pisanih za 36. kongres o klimatizaciji, grejanju, hladenju + CD-ROM./ Proceedings of the 36th International HVAC&R congress + CD-ROM.
View record
-
Optimierung der Akustik und der Effizienz von A...
- Author(s) : DIETLE J., NEUMEIER R.
- Date : 2006/11/22
- Languages : German
- Source: DKV-Tagungsbericht 2006, Dresden.
View record
-
MECHANICAL FLOW RATE CONTROL OF FANS.
- Author(s) : CASSEE C. F.
- Date : 1982/12
- Languages : Dutch
- Source: Klimaatbeheersing - vol. 11 - n. 12
View record