Research on calculation method of thermal design load in air conditioning systems.

Author(s) : ISHINO H.

Type of article: Periodical article

Summary

The purpose is to develop a simplified estimation method. The author newly defined the 2.5% risk level load obtained from hour-by-hour dynamic simulation over one year as the design peak load, and also defined the operative temperature corresponding to the 2.5% risk load as the design operative temperature. The design of experiment method was developed for the simple estimation of 2.5% risk level design load and design of operative temperature. The author analyzed the characteristics of the conventional daily periodical design load compared to the 2.5% risk level design load.

Details

  • Original title: Research on calculation method of thermal design load in air conditioning systems.
  • Record ID : 1996-2399
  • Languages: English
  • Source: Mem. Fac. Eng. Tokyo metrop. Univ. - n. 44
  • Publication date: 1994
  • Document available for consultation in the library of the IIR headquarters only.

Links