THE FEASIBILITY STUDY OF HIGH CRITICAL TEMPERATURE SUPERCONDUCTING POWER CABLE.

[In Japanese. / En japonais.]

Author(s) : ICHIYANAGI N.

Type of article: Article

Summary

WHEN SUPERCONDUCTING OXIDES, WHICH HAVE SMALLER LOWER-CRITICAL FIELD VALUES, HC, ARE APPLIED TO A HEAVY-CURRENT POWER TRANSMISSION CABLE, ITS OPERATION IN THE SURFACE CURRENT REGION IS IMPOSSIBLE. FOR A LARGE ALTERNATING CURRENT CAPACITY WITH A RESTRICTED CABLE DIAMETER, OPERATION IN THE REGION ABOVE HC IS REQUIRED FOR AN OXIDE CABLE. IN THE STUDY, THE ALTERNATING CURRENT LOSS FOR AN OXIDE CABLE AT LIQUID-NITROGEN TEMPERATURE IS CALCULATED BY USING THE BEAN MODEL. THE RESULT INDICATES THAT, FOR A 60 MM DIAMETER CONDUCTOR, CRITICAL CURRENT DENSITIES, 10,000 AND 100,000 A/CM2 OF OXIDE SUPERCONDUCTORS ARE REQUIRED FOR 5,000 AND 10,000 A CURRENT-CAPACITY CABLES, RESPECTIVELY.

Details

  • Original title: [In Japanese. / En japonais.]
  • Record ID : 1991-0051
  • Languages: Japanese
  • Source: Cryogenics/ Cryog. Eng. - vol. 25 - n. 1
  • Publication date: 1990
  • Document available for consultation in the library of the IIR headquarters only.

Links


See other articles in this issue (2)
See the source