Document IIF

Applications du cycle transcritique au CO2 en froid commercial de faible puissance.

The transcritical CO2 cycle in light commercial refrigeration applications.

Auteurs : VEJE C., SÜSS J.

Résumé

For light commercial systems, a solution with CO2 is to use the transcritical cycle. It is well known that active control of the system high pressure must be applied for transcritical CO2 cycles to obtain good cycle efficiencies. This paper describes the implementation and performance measurements of light commercial refrigeration applications. The authors compare the results to baseline R134a systems and relate the results to steady state analysis. With a change from capillary tube R134a systems to a CO2 system with a control valve, the authors found energy reductions up to 37% depending on application and conditions.

Documents disponibles

Format PDF

Pages : 2004-2

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : The transcritical CO2 cycle in light commercial refrigeration applications.
  • Identifiant de la fiche : 2005-2595
  • Langues : Anglais
  • Source : Natural Working Fluids 2004: 6th IIR-Gustav Lorentzen Conference
  • Date d'édition : 01/08/2004

Liens


Voir d'autres communications du même compte rendu (105)
Voir le compte rendu de la conférence