Évaluation des risques d’un meuble frigorifique de vente (MFV) intégré utilisant un frigorigène de classe A3.
Risk assessment of built-in refrigerated display cabinet using A3 refrigerant.
Numéro : No 122
Auteurs : YAMASHITA K., SAKAMOTO Y., KATO T., ISHIHARA S., KOBAYASHI A., KAINUMA H., HASEGAWA T., NAGAI H., HOSAKA K.
Résumé
In Japan, from 2011 to 2016, risk assessment of each type of equipment using A2L refrigerants was carried out and JRAIA standards which prescribed safe operating method were created, resulting in the relaxation of law was realized. In order to respond to demand in recent years to further lower GWP, risk assessment of builtin refrigerated display cabinet using A3 refrigerants was carried out. CFD analyses on refrigerant leakage from inside or outside the refrigerated space of each refrigerated display cabinet was carried out, the flammable volume was calculated, the ignition sources were investigated, and the ignition probability was calculated. Risk assessments were carried out at each stage of transportation, storage, installation, usage, service, and disposal. In this paper, the contents of the study and safe operating method created as a result are summarized.
Documents disponibles
Format PDF
Pages : 11 p.
Disponible
Gratuit
Détails
- Titre original : Risk assessment of built-in refrigerated display cabinet using A3 refrigerant.
- Identifiant de la fiche : 30029994
- Langues : Anglais
- Sujet : Technologie
- Source : 13th IEA Heat Pump Conference 2021: Heat Pumps – Mission for the Green World. Conference proceedings [full papers]
- Date d'édition : 31/08/2021
Liens
Voir d'autres communications du même compte rendu (198)
Voir le compte rendu de la conférence
Indexation
-
Study on method ensuring safety of built-in ref...
- Auteurs : YAMASHITA K., SAKAMOTO Y., KATO T., et al.
- Date : 24/08/2019
- Langues : Anglais
- Source : Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
- Formats : PDF
Voir la fiche
-
A3 refrigerant R290 leak and ignition testing f...
- Auteurs : WANG X.
- Date : 26/08/2020
- Langues : Anglais
- Source : 6th IIR International Conference on Sustainability and the Cold Chain. Proceedings: Nantes, France, August 26-28 2020
- Formats : Vidéo, PDF
Voir la fiche
-
Study on CFD analysis of refrigerant leakage an...
- Auteurs : YAMASHITA K., SAKAMOTO Y., KATO T., et al.
- Date : 18/06/2018
- Langues : Anglais
- Source : 13th IIR Gustav Lorentzen Conference on Natural Refrigerants (GL2018). Proceedings. Valencia, Spain, June 18-20th 2018.
- Formats : PDF
Voir la fiche
-
Theoretical and simulation analysis for R290 le...
- Auteurs : NING Q., HE G., LI B., LI T.
- Date : 10/2024
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 166
- Formats : PDF
Voir la fiche
-
Computational fluid dynamics analysis of flamma...
- Auteurs : ZHANG S., CHEN G., LI Z., FANG J.
- Date : 02/2022
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 134
- Formats : PDF
Voir la fiche