A PD law based fuzzy logic control strategy for simultaneous control of indoor temperature and humidity using a variable speed direct expansion air conditioner.
Number: pap. 2154
Author(s) : LI Z., XU X. G., DENG S. M., et al.
Summary
In small to medium scale buildings located in the subtropics, such as Hong Kong, direct expansion air conditioning (DX A/C) systems are widely applied. This is because, as compared to chilled water based central air conditioning systems, DX A/C systems are compact, flexible for multi-room services, energy efficient and cost less to maintain and operate. However, traditionally, a DX A/C system is equipped with a single-speed compressor and supply air fan, and employs ON / OFF control strategy to maintain indoor air temperature only, leaving the indoor moisture content (or relative humidity) uncontrolled. With the introduction of variable speed technology, the speeds of compressor and supply air fan can be varied continuously so as to realize the simultaneous control of the indoor temperature and humidity. In this paper, the development of a novel control strategy based on PD law and fuzzy logic is reported. The compressor speed was adjusted directly according to the indoor air moisture content and supply air fan speed according to the indoor air dry-bulb temperature, respectively, to realize the simultaneous control of indoor air temperature and humidity. Controllability tests for the novel control strategy were carried out and the test results suggested that, although two control loops for temperature and humidity were significantly coupled, the simultaneous control of indoor temperature and humidity was achieved with respect to control accuracy and sensitivity.
Available documents
Format PDF
Pages: 10 p.
Available
Public price
20 €
Member price*
15 €
* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).
Details
- Original title: A PD law based fuzzy logic control strategy for simultaneous control of indoor temperature and humidity using a variable speed direct expansion air conditioner.
- Record ID : 30013270
- Languages: English
- Source: 2014 Purdue Conferences. 15th International Refrigeration and Air-Conditioning Conference at Purdue.
- Publication date: 2014/07/14
Links
See other articles from the proceedings (203)
See the conference proceedings
-
Experimental study on temperature-humidity sepa...
- Author(s) : WENG W., XU Y., WANG T.
- Date : 2014/11
- Languages : Chinese
- Source: HV & AC - vol. 44 - n. 297
- Formats : PDF
View record
-
Inherent operational characteristics and operat...
- Author(s) : XIA Y., DENG S., CHAN M. Y.
- Date : 2017/02/25
- Languages : English
- Source: Applied Thermal Engineering - vol. 113
View record
-
A novel proportional-derivative (PD) law based ...
- Author(s) : LI Z., XU X., DENG S., et al.
- Date : 2015/09
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 57
- Formats : PDF
View record
-
Inherent correlation between the total output c...
- Author(s) : XU X., XIA L., CHAN M., et al.
- Date : 2010/09
- Languages : English
- Source: Applied Thermal Engineering - vol. 30 - n. 13
View record
-
Analysis and application of evaluation method o...
- Author(s) : ZHANG H., WU J., LI Y.
- Date : 2013/02
- Languages : Chinese
- Source: Journal of Refrigeration - vol. 34 - n. 149
- Formats : PDF
View record