A TALE OF 2 CONTROL SYSTEMS.
Author(s) : MCMASTERS R. L.
Type of article: Article
Summary
THE PAPER OFFERS AN IMPROVED SYSTEM OF REHEAT CONTROL FOR A SI MPLE AIR-CONDITIONING PLANT. THE NORMAL SYSTEM USES A HUMIDISTAT SENSOR TO LOWER COOLING COIL TEMPERATURE ON A RISE IN SPACE HUMIDITY. SPACE TEMPERATURE THEN DROPS TO THE LOW END OF THE TEMPERATURE CONTROLLER PROPORTIONAL BAND BEFORE REHEAT OPERATES. THE SUGGESTED SYSTEM USES A HUMIDISTAT SENSOR TO BRING ON THE REHEAT COIL IN A SIMILAR SITUATION, EFFECTIVELY RAISING TEMPERATURE AND CAUSING AN IMMEDIATE ACTION FROM THE TEMPERATURE CONTROLLER TO INCREASE COOLING. THE REQUIRED EFFECT ON HUMIDITY AND TEMPERATURE WILL LAY IN A NARROWER BAND. D.W.H.
Details
- Original title: A TALE OF 2 CONTROL SYSTEMS.
- Record ID : 1991-1294
- Languages: English
- Source: Heat. Pip. Air Cond. - vol. 62 - n. 9
- Publication date: 1990/09
- Document available for consultation in the library of the IIR headquarters only.
Links
See other articles in this issue (5)
See the source
Indexing
- Themes: Other air-conditioning equipment
- Keywords: Automation; Humidity; Control (generic); Air conditioning
-
CHARACTERISTICS OF A CONTROL AND MONITORING LAN...
- Author(s) : RENI R., LETTINA C.
- Date : 1987/03
- Languages : Italian
- Source: Cond. Aria - vol. 31 - n. 3
View record
-
THE USE OF DIRECT DIGITAL CONTROLS IN THE HVAC ...
- Author(s) : WATT R. C.
- Date : 1989
- Languages : English
- Source: AIRAH J. - vol. 43 - n. 12
View record
-
A NEW AIR CONDITIONING ENVIRONMENTAL CONTROL ME...
- Author(s) : SUGAWARA S., HARA M.
- Date : 1990
- Languages : English
- Source: Energy Build. - vol. 14 - n. 3
View record
-
MICROPROCESSOR-BASED CONTROL SYSTEM AND THEIR I...
- Author(s) : BABIAK R.
- Date : 1984/09
- Languages : English
- Source: Aust. Refrig. Air Cond. Heat. - vol. 38 - n. 9
View record
-
FAN REDUCES THE QUANTITY OF AIR.
- Author(s) : PAUL L.
- Date : 1991/08
- Languages : German
- Source: Heiz. Lüft.-Klima Haustech. - vol. 42 - n. 8
View record