IIR document
Centrifugal chillers: thermodynamic modelling and a diagnostic case study.
Author(s) : GORDON J. M., NG K. C., CHUA H. T.
Type of article: Article, IJR article
Summary
The diagnostic capability of a simple thermodynamic model for chiller performance is illustrated by a case study for a commercial, installed centrifugal chiller. Performance data were measured both prior to, and subsequent to, chiller maintenance that improved chiller efficiency. Using these experimental measurements, the authors show that the simple thermodynamic model, originally developed for reciprocating and absorption chillers, succeeds in predicting the fundamental relation between COP and cooling rate for the centrifugal chiller, and permits a clear diagnostic analysis of heat exchanger fouling on chiller performance.
Available documents
Format PDF
Pages: 253-257
Available
Public price
10 €
Member price*
Free
* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).
Details
- Original title: Centrifugal chillers: thermodynamic modelling and a diagnostic case study.
- Record ID : 1995-3512
- Languages: English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 18 - n. 4
- Publication date: 1995/05
Links
See other articles in this issue (6)
See the source