Experimental investigation on heat transfer of spray cooling with isobutane (R600a).

Author(s) : XU H., SI C. Q., SHAO S., et al.

Type of article: Article

Summary

In order to enhance the heat transfer performance of spray cooling system, an integrated system is developed. The system is based on the refrigeration cycle, and uses isobutane (R600a) as the coolant. The heat transfer performance, such as the heat surface temperature, the heat transfer coefficient and the surface temperature distribution, are experimentally investigated in this paper. When the coolant mass flow rate is nearly 6.9 kg/h, the surface temperature can be kept at 57.3°C with the heat flux of 145 W/
cm2. The heat transfer coefficient can be achieved up to 35,000 W/(m2°C) when the nozzle inlet pressure and the chamber pressure are 4.9 bar and 2.3 bar, respectively. The surface temperature uniformity is mainly influenced by the mass flow rate, the heat flux and the nozzle inlet pressure together, and the standard deviation of the surface temperature is less than 4.0°C in this study. All the results indicate that this system is promising in the application for high heat flux removal.