EXPERIMENTAL STUDIES TO DETERMINE THE EFFECT OF ABSORBER REFLUX ON THE PERFORMANCE OF A WATER-LITHIUM BROMIDE ABSORPTION COOLER.

Author(s) : EISA M. A. R.

Type of article: Article

Summary

ILLUSTRATES SCHEMATICALLY AN EXPERIMENTAL ABSORPTION COOLER AND DESCRIBES THE EXPERIMENTS CARRIED OUT. THE REFLUX RATIO WAS VARIED FOR TWO MASS FLOW RATES OF SOLUTION LEAVING THE ABSORBER AND TWO ABSORBER TEMPERATURES. FINDS THAT THE ABSORBER REFLUX CAN BE USED TO DECREASE BOTH THE TEMPERATURE AND THE CONCENTRATION IN THE GENERATOR. THE COP AND HEAT LOADS TEND TO HAVE OPTIMUM VALUES AT A PARTICULAR REFLUX RATIO. EU(INT. BUILD. SERV. ABSTR., GB., 22, N 1, 1987, 15, 87-00147.

Details

  • Original title: EXPERIMENTAL STUDIES TO DETERMINE THE EFFECT OF ABSORBER REFLUX ON THE PERFORMANCE OF A WATER-LITHIUM BROMIDE ABSORPTION COOLER.
  • Record ID : 1987-1787
  • Languages: English
  • Source: Int. J. Energy Res. - vol. 10 - n. 4
  • Publication date: 1986/10
  • Document available for consultation in the library of the IIR headquarters only.

Links