Experimental study on performance of segmented handling air-conditioning system under part load conditions.

[In Chinese. / En chinois.]

Author(s) : JIANG X., LIANG C.

Type of article: Article

Summary

Air conditioning systems are usually operated under part load conditions, and segmented handling air-conditioning system has significant advantages of realizing energy-saving operation under part load conditions. Chillers in serial configuration was carried out on a test bed of segmented handling air-conditioning system, and the performance of system in different load conditions were studied. Experiment results show that: the maximum load that segmented handling air-conditioning system can handle is only 81.5% compared with conventional systems when the design load is the same. When the load reduces from 81.5% to 50%, the chillers of the system average COP increases from 3.13 to 4.16, which indicates that segmented handling air conditioning system can create a big energy saving potential under part load conditions.

Available documents

Format PDF

Pages: 25-29, 48

Available

  • Public price

    20 €

  • Member price*

    15 €

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details


Links


See other articles in this issue (4)
See the source