INDUCTION UNITS WITH IMPROVED ROOM AIR FLOW.
[In German. / En allemand.]
Author(s) : ROTH H. W.
Type of article: Article
Summary
DATA ARE GIVEN FOR OPTIMAL DESIGN AND INSTALLATION OF INDUCTION UNITS BELOW WINDOWS SILLS OF OFFICES TO OBTAIN GOOD THERMAL COMFORT. THE COOLING CAPACITY IN RELATION TO THE FLOOR SPACE SHOULD BE LESS THAN 60-70 WATTS/M2. THE NOMINAL AIR RATE VARIES, DEPENDING ON SIZE, BETWEEN 1.5 TO 3.5 CHANGES PER HOUR. IF HIGHER COOLING POWER OF UP TO 100 WATTS/M2, IS NECESSARY, POWER JETS IN THE CEILING OR INDUCTION UNITS WITH VARIABLE SUPPLY AIR RATES SHOULD BE USED. MAXIMUM AIR VELOCITIES ARE LOWER THAN THE LIMITS GIVEN IN DIN 1946/2.
Details
- Original title: [In German. / En allemand.]
- Record ID : 1990-2540
- Languages: German
- Source: Klima Kälte Heiz. - vol. 17 - n. 11
- Publication date: 1989
- Document available for consultation in the library of the IIR headquarters only.
Links
See other articles in this issue (3)
See the source
Indexing
- Themes: Comfort air conditioning
- Keywords: Office; Enhancement; Building; Ventilation; Design; Optimization; Thermal comfort; Air conditioning
-
Hoe geven we bestaande kantoren een hoog comfort?
- Author(s) : RUIJSSCHER L. de, LEDE F. de
- Date : 2006/11
- Languages : Dutch
- Source: Koude & Luchtbehandeling - vol. 99 - n. 11A
View record
-
Die Fachwelt Staunt, die Kunden Jubeln.
- Date : 2008/01/04
- Languages : German
- Source: CCI Zeitung - vol. 42 - n. 01
View record
-
Single-sided natural ventilation: how deep an o...
- Author(s) : WALKER R. R., WHITE M. K.
- Date : 1992
- Languages : English
- Source: Build. Serv. Eng. Res. Technol. - vol. 13 - n. 4
View record
-
INNOVATION ET GRAND CHANTIER : UN EXEMPLE A LA ...
- Author(s) : TERNANT C.
- Date : 1989/05
- Languages : French
View record
-
AIR CONDITIONING PLANT FOR OFFICE BUILDINGS.
- Author(s) : AMMAN L. E.
- Date : 1987/12
- Languages : Italian
- Source: Cond. Aria - vol. 31 - n. 12
View record