Integration of an expander into a CO2 refrigeration system.

Integration einer Expansionsmaschine in ein CO2-Kältesystem.

Author(s) : QUACK H., KRAUS W. E., NICKL J., et al.

Type of article: Article

Summary

An expander with work recovery improves the COP of transcritical CO2 refrigeration cycles. If one chooses a three-stage expander, it is advantageous to introduce a vapour-liquid separator between the second and third stage of refrigeration. The separated vapour is expanded in the third stage of the expander, whereas the liquid flows at a medium pressure level to the cooling stations, where it is throttled by a thermostatic or electronic expansion valve.

Details

  • Original title: Integration einer Expansionsmaschine in ein CO2-Kältesystem.
  • Record ID : 2005-0667
  • Languages: German
  • Source: KI Luft Kältetech. - vol. 40 - n. 9
  • Publication date: 2004/09

Links


See other articles in this issue (4)
See the source