Low GWP refrigerant application for the centrifugal chiller - study for application of HFO-1234ze(E).

[In Japanese. / En japonais.]

Author(s) : UEDA K., WAJIMA K., YOKOYAMA A., et al.

Type of article: Article

Summary

The authors have installed HFO-1234ze(E) and evaluated the basic characteristics by using a centrifugal chiller. The cooling capacity with HFO-1234ze(E) is smaller than with HFC-134a to 70 %, at same refrigerant gas volume flow. The COP with at rated capacity is less than that of HFC-134a by 6-3 %.

Details

  • Original title: [In Japanese. / En japonais.]
  • Record ID : 30003436
  • Languages: Japanese
  • Source: Transactions of the Japan Society of Refrigerating and Air Conditioning Engineers - vol. 28 - n. 4
  • Publication date: 2011