Low GWP refrigerant application for the centrifugal chiller - study for application of HFO-1234ze(E).
[In Japanese. / En japonais.]
Author(s) : UEDA K., WAJIMA K., YOKOYAMA A., et al.
Type of article: Article
Summary
The authors have installed HFO-1234ze(E) and evaluated the basic characteristics by using a centrifugal chiller. The cooling capacity with HFO-1234ze(E) is smaller than with HFC-134a to 70 %, at same refrigerant gas volume flow. The COP with at rated capacity is less than that of HFC-134a by 6-3 %.
Details
- Original title: [In Japanese. / En japonais.]
- Record ID : 30003436
- Languages: Japanese
- Source: Transactions of the Japan Society of Refrigerating and Air Conditioning Engineers - vol. 28 - n. 4
- Publication date: 2011
Links
See other articles in this issue (8)
See the source
Indexing
-
How to minimize TEWI: case history with oil fre...
- Author(s) : FADIGA F.
- Date : 2018/09
- Languages : English
- Source: 1st IIR international conference on the application of HFO refrigerants, Birmingham, September 2-5 2018.
- Formats : PDF
View record
-
How to minimize TEWI: case history with oil fre...
- Author(s) : FADIGA F.
- Date : 2018/09
- Languages : English
- Source: 1st IIR international conference on the application of HFO refrigerants, Birmingham, September 2-5 2018.
- Formats : PDF
View record
-
Energy-conservation system applied to centrifug...
- Author(s) : HASEGAWA Y., UEDA K., MATSUO M., et al.
- Date : 2011/03
- Languages : Japanese
- Source: Refrigeration - vol. 86 - n. 1001
View record
-
Low GWP chillers development.
- Author(s) : ACHAICHIA N., MATTEO G.
- Date : 2015/06/12
- Languages : English
- Source: Le ultime tecnologie del freddo e del condizionamento. Atti del 16° Convegno Europeo: June 12-13, 2015, Milano, Italia.
- Formats : PDF
View record
-
Performance monitoring of centrifugal chillers.
- Author(s) : BANSAL P. K., JAGER C. R.
- Date : 1995/05/01
- Languages : English
- Source: 1995 AIRAH Conference Proceedings.
View record