Low GWP refrigerant application for the centrifugal chiller - study for application of HFO-1234ze(E).
[In Japanese. / En japonais.]
Author(s) : UEDA K., WAJIMA K., YOKOYAMA A., et al.
Type of article: Article
Summary
The authors have installed HFO-1234ze(E) and evaluated the basic characteristics by using a centrifugal chiller. The cooling capacity with HFO-1234ze(E) is smaller than with HFC-134a to 70 %, at same refrigerant gas volume flow. The COP with at rated capacity is less than that of HFC-134a by 6-3 %.
Details
- Original title: [In Japanese. / En japonais.]
- Record ID : 30003436
- Languages: Japanese
- Source: Transactions of the Japan Society of Refrigerating and Air Conditioning Engineers - vol. 28 - n. 4
- Publication date: 2011
Links
See other articles in this issue (8)
See the source
Indexing
-
Energy-conservation system applied to centrifug...
- Author(s) : HASEGAWA Y., UEDA K., MATSUO M., et al.
- Date : 2011/03
- Languages : Japanese
- Source: Refrigeration - vol. 86 - n. 1001
View record
-
Application of total heat recovery water chillers.
- Author(s) : LIN X.
- Date : 2011/05
- Languages : Chinese
- Source: HV & AC - vol. 41 - n. 250
- Formats : PDF
View record
-
ENHANCEMENT OF THE EFFICIENCY OF CENTRIFUGAL RE...
- Author(s) : SUHOMLINOV I. Ja.
- Date : 1988
- Languages : Russian
- Source: Kholodilnaya Tekhnika - n. 9
View record
-
Gruppi frigoriferi ad alta efficienza.
- Author(s) : VIO M.
- Date : 2004/12
- Languages : Italian
- Source: Cond. Aria - n. 11
View record
-
Experimental study on hydraulic performance and...
- Date : 2025/01
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 169
- Formats : PDF
View record