MECHANICAL SUBCOOLING IMPROVES SUPERMARKET REFRIGERATION PERFORMANCE.

Author(s) : BAHEL V., ZUBAIR S. M.

Type of article: Article

Summary

THE ARGUMENT PUT FORWARD APPLIES EQUALLY TO REFRIGERATION SYSTEMS OTHER THAN SUPERMARKETS PROVIDING THEY OPERATE NORMALLY WITH FAIRLY HIGH CONDENSING TEMPERATURES. THE CASE TAKEN IS FOR AIR-COOLED CONDENSERS IN THE MIDDLE EAST. IF A SMALL REFRIGERATION SYSTEM IS ADDED TO SUBCOOL THE MAIN SYSTEM CONDENSATE FLOW TO ABOUT 283 K (10 DEG C) WHILE EVAPORATING AT A MUCH HIGHER TEMPERATURE THAN THE MAIN PLANT, SUBSTANTIAL POWER SAVINGS ARE POSSIBLE. RETROFITTING OF SUCH A SYSTEM IS RELATIVELY SIMPLE, AS THE EXISTING CONDENSER CAN ACCOMODATE THE SUBCOOLING SYSTEM CONDENSING DUTY AND STILL BE OVERSIZED DUE TO THE INCREASE IN EFFICIENCY OF THE MAIN PLANT. D.W.H.

Details

  • Original title: MECHANICAL SUBCOOLING IMPROVES SUPERMARKET REFRIGERATION PERFORMANCE.
  • Record ID : 1989-0265
  • Languages: English
  • Source: Heat. Pip. Air Cond. - vol. 60 - n. 2
  • Publication date: 1988/02
  • Document available for consultation in the library of the IIR headquarters only.