WATER-COOLED AIR CONDITIONING SYSTEMS FOR ENERGY AND POWER SAVING.
Author(s) : SURI R. K.
Type of article: Article
Summary
PRESENTS THE RESULTS OF AN EXPERIMENTAL INVESTIGATION TO COMPARE THE PERFORMANCE IN THE CLIMATE OF KUWAIT OF WATER-COOLED AND AIR-COOLED AIR CONDITIONING SYSTEMS. STATES THAT 2 IDENTICAL CHILLED WATER AIR CONDITIONING SYSTEMS INCORPORATING AIR-COOLED AND WATER-COOLED CONDENSERS, WERE USED INDEPENDENTLY TO SUPPLY THE COOLING DEMAND OF A SPACE. THE WATER-COOLED SYSTEM REQUIRES 40% LESS PEAK POWER AND 25% LESS ELECTRICAL ENERGY. THE ENERGY REQUIREMENTS CAN BE REDUCED FURTHER IF SEA WATER IS USED FOR CONDENSER COOLING IN PLACE OF DESALINATED SEA WATER. (INT. BUILD. SERV. ABSTR., GB., 24, N 5, 1989/09-10, 89-01451.
Details
- Original title: WATER-COOLED AIR CONDITIONING SYSTEMS FOR ENERGY AND POWER SAVING.
- Record ID : 1990-1275
- Languages: English
- Source: Int. J. ambient Energy - vol. 10 - n. 3
- Publication date: 1989/07
- Document available for consultation in the library of the IIR headquarters only.
Links
See other articles in this issue (1)
See the source
Indexing
-
Effect of ambient conditions in Kuwait on the p...
- Author(s) : WALY M., CHAKROUN W., MUTAWA N. K. al-
- Date : 2005/11/21
- Languages : English
- Source: ICERD-3. Third International Conference on Energy Research and Development [2 volumes + CD-ROM].
View record
-
THE USE OF HEAT RECOVERY EQUIPMENT IN DESERT EN...
- Author(s) : HOLLAND B.
- Date : 1987
- Languages : English
- Source: Heat Recov. Syst. CHP - vol. 7 - n. 5
View record
-
Substitution of MSF desalting plants with absor...
- Author(s) : DARWISH M. A.
- Date : 2002
- Languages : English
- Source: ASHRAE Transactions. 2002 annual Meeting, Honolulu, Hawaii. Volume 108, part 2 + CD-ROM.
View record
-
INDIRECT EVAPORATIVE COOLING USING PLATE TYPE H...
- Author(s) : SCOFIELD C. M., DESCHAMPS N. H.
- Date : 1984
- Languages : English
View record
-
THE USE OF HEAT RECOVERY EQUIPMENT IN DESERT EN...
- Author(s) : HOLLAND B.
- Date : 1987/04
- Languages : English
- Source: H&V Eng. - vol. 60 - n. 682
View record