IIR document

Optimal configuration of compressors in industrial refrigeration systems based on part-load.

Number: pap. n. 50

Author(s) : ZHANG J., WEI D.

Summary

A typical industrial refrigerating plant is selected for analysis. The operational regulation of the compressors over an annual period is determined. The ratio between refrigerating capacity of the operating compressors and total compressor capacity is calculated and defined as the part-load ratio of the plant. It is found that the plant was operating at 30% part-load for 66.4% of the annual operating time. Some measures for optimal configuration of compressors based on part-load are proposed to improve annual energy efficiency. A case study further reveals that optimal configuration of compressors will not only decrease operational costs, but also decrease capital investment requirements of the plant.

Available documents

Format PDF

Pages: 5 p.

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Optimal configuration of compressors in industrial refrigeration systems based on part-load.
  • Record ID : 30015084
  • Languages: English
  • Source: Proceedings of the 24th IIR International Congress of Refrigeration: Yokohama, Japan, August 16-22, 2015.
  • Publication date: 2015/08/16
  • DOI: http://dx.doi.org/10.18462/iir.icr.2015.0050

Links


See other articles from the proceedings (657)
See the conference proceedings